Question
Why is my analog 4-20mA sensor showing the error device not ready?
Answer
If your 4-20mA sensor is connected to a Solo, it is likely the POWER field in the configuration is set to "Output1" instead of "Default". Change the field to "Default" from the Device Settings in Manage Equipment and the error should be resolved: