Description
The C3+ can remotely control and monitor a diesel engine via the Murphy PowerCore® TEC-10 engine controller as explained in this Technical Note. The installation of the Murphy TEC-10 is not detailed in this article, this should be carried out by a qualified technician. This article focuses on the interface between the C3+ and TEC-10 Controller. Observant will provide support ONLY for the configuration of the C3+.
Remote control capability should not replace local on/off control or any other fail-safe hardware. An Emergency Stop button and appropriate power disconnects should always be in place at the same location as the Engine.
Applications
The Murphy TEC-10 is an engine controller for electronic and mechanical engines, with additional pump monitoring functionality.
Full Diesel Engine Automation with the following Protections:
- Engine Oil Pressure
- Engine Coolant Temperature
- Engine Overspeed
- Battery Voltage Low and High
- Alternator Charge Warning
AutoStart and Stop Capabilities:
- Single Contact (2 wire, dry contact)
- Telemetry
- Discharge Pressure High and Low
- Level High and Low
- Floats
Throttle Automation Capabilities (requires Variable Speed Kit):
- Maintain Discharge Pressure Setpoint
- Automated Warm Ups and Cooldowns
- 4x RPM Maintain Setpoints
As part of an Observant system, the device can show:
- Engine Speed
- Faults
- Engine Run Hours
- Oil Pressure
- Engine Temperature
- Battery Voltage
- Controller Mode
The engine can be started and stopped remotely and the RPM set-point can be adjusted.
Electrical Connection and Installation
The C3+ should be located as close as possible to the controller.
Configuration
TEC-10 Modbus Menu Settings
The TEC-10 Communications settings for Modbus can be found in the Controller menu (Password: 3482) under “Communication.”
- Set the Communication Type to "Modbus".
- Set the TEC-10 Modbus Slave Address to 1.
- Go to "Serial Setup":
- Set the Baud-rate to 19200.
- Set the Stop-bits to 1.
- Set the parity to "None".
- Go to "Application Configuration":
- Set Auto Start/Stop Function to "Local Start".
Please note that Remote Start via the C3+ Telemetry Unit is only available when the TEC-10 Control Panel is in Auto-mode.
If the TEC-10 is not in Auto-mode, press-hold the Auto Key for 3 seconds.
Adding in Global
The Murphy TEC-10 can be found under the "Engine Control" category when adding a new device in Manage Equipment.